- Date
- 09/06/2017
- W/O
- 654302
- Weather
- Dry
- Operator/Surveyor
- CORTEZ ESTEBAN
- Sewer ID
- Z00028
- PipeID
- P11272
- Time
- 11:43 PM
- Certificate
- U-209-8148
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4917
- Sewer Name
- E JOINT OUTFALL E - UNIT 2
- City
- W COMPTON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 16
- Purpose
- Routine Assessment
- Project
- WO_654302_TV01123_AUG2017
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 48 in.
- Width
- 48 in.
- Upstream MH
- E 0044
- Downstream MH
- E 0045
- Dir. of Survey
- Upstream
- Length Surveyed
- 383.6 ft.
- Total Length
- 383.6 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 3
- O&M Quick
- 3121
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 8
Pipe schematic from manhole E 0044 to E 0045 Observation photos (3)

1.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

383.6 ft. - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS

383.6 ft. - Survey Abandoned - A/S SEVERE DEBRIS