- Date
- 09/26/2017
- W/O
- 657837
- Weather
- Dry
- Operator/Surveyor
- CORTEZ ESTEBAN
- Sewer ID
- Z00013
- PipeID
- P00356
- Time
- 11:36 PM
- Certificate
- U-209-8148
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4941
- Sewer Name
- 08 KEYSTONE TRUNK
- City
- CARSON
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- WO_657837_TV08155_SEP2017
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 08 0309
- Downstream MH
- 08 0308
- Dir. of Survey
- Downstream
- Length Surveyed
- 325.7 ft.
- Total Length
- 325.7 ft.
- Structural Index
- 2
- Structural Quick
- 2300
- Structural Rating
- 6
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 6
Pipe schematic from manhole 08 0309 to 08 0308 Observation photos (3)

16.6 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

34.7 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

36.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start