Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2017, 10:36 AM
  • 14 0199_14 0198 _09192017_033709.mp4

Date
09/19/2017
W/O
657830
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18238
Time
3:36 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4728
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_657830_TV14033_SEP2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
14 0199
Downstream MH
14 0198
Dir. of Survey
Downstream
Length Surveyed
354.3 ft.
Total Length
354.3 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 14 0199 to 14 0198
MH: 14 0199MH: 14 0198downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 01992 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start15 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"35.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"80.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"138.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"144.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"207.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"237.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"266.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"330.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"337.9 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES338.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"352.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish353 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH354.3 ft. AMH - Downstream Manhole, Survey Ends - 14 0198

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    337.9 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
2CM
35.8TFC
330.3TFA
353MGOSPALLING THROUGHOUT THE REACH
144.1TFA
338.9TFC
352.8DAGS
80.9TFA
15TFA
266.7TFA
237.2TFC
207.3TBA
0MWL
2DAGS
138.6TFC
0MWM
354.3AMH14 0198
0AMH14 0199
337.9FM

Properties (5)

additional_info
SC345741
custom_field_two
3
customer
LACSD
datetime
2017-09-19T03:36:46-07:00
sewer_category
Gravity