Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 19, 2017, 08:53 AM
  • 18 0734_18 0733 _20170519_020511.mp4

Date
05/19/2017
W/O
635639
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00706
PipeID
P14587
Time
1:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4500
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_635639_TV18103_MAY2017
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0734
Downstream MH
18 0733
Dir. of Survey
Downstream
Length Surveyed
313.4 ft.
Total Length
313.4 ft.
Structural Index
3
Structural Quick
5B2K
Structural Rating
198
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 18 0734 to 18 0733
MH: 18 0734MH: 18 0733downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 073419.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start168.1 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO199.9 ft. SRV - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO234.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start304.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish313.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0733313.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

    168.1 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

    199.9 ft. - Surface Reinforcement Visible, from 01 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    234.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

Observations (11)

DistanceCodeObservation
168.1SRV
0MGOCONNECTION AT MH 3 O'CLOCK
304.1SRV
19.3SSS
0MWM
0MWL
313.4AMH18 0733
199.9SRV
0AMH18 0734
234.1SRV
313.4SSS

Properties (5)

additional_info
SC345310
custom_field_two
2
customer
LACSD
datetime
2017-05-19T01:53:25-07:00
sewer_category