- Date
- 05/18/2017
- W/O
- 635639
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00706
- PipeID
- P14604
- Time
- 11:00 PM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4500
- Sewer Name
- 18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 26
- Purpose
- Routine Assessment
- Project
- WO_635639_TV18103_MAY2017
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Width
- 30 in.
- Upstream MH
- 18 0750A
- Downstream MH
- 18 0750
- Dir. of Survey
- Downstream
- Length Surveyed
- 212.5 ft.
- Total Length
- 212.5 ft.
- Structural Index
- 4
- Structural Quick
- 5H3H
- Structural Rating
- 357
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 357
Pipe schematic from manhole 18 0750A to 18 0750 Observation photos (7)

2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

53.8 ft. - Hole Void Visible, from 04 to 05 o'clock, within 8 inches of joint: NO

56 ft. - Hole Soil Visible, from 04 to 05 o'clock, within 8 inches of joint: NO

67.6 ft. - Hole Soil Visible, at 04 o'clock, within 8 inches of joint: NO

110.1 ft. - Hole, at 04 o'clock, within 8 inches of joint: NO

211 ft. - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO