Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2016, 09:10 AM
  • 19 0089_19 0088_20160317_024155.mp4

Date
03/17/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15281
Time
2:10 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3227
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0089
Downstream MH
19 0088
Dir. of Survey
Downstream
Length Surveyed
328.4 ft.
Total Length
328.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 19 0089 to 19 0088
MH: 19 0089MH: 19 0088downstream0 ft. AMH - Upstream Manhole, Survey Begins - 19 00890 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MWM - Water Mark, 65 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area7.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start68.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"78.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"81 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"118.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"158.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"160 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 4"168.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"173.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"210.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"217.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"267.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"302.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"312.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"322.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"325.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.4 ft. AMH - Downstream Manhole, Survey Ends - 19 0088

Observations (21)

DistanceCodeObservation
173.5TFA
78.5TFC
160TBA
302.9TFA
168.5TFC
217.9TFC
312.6TFA
81TBA
68.2TFA
328.4AMH19 0088
0AMH19 0089
0MGOLATERAL AT MH 3 OCLOCK
322.6TFA
325.8DAGS
7.5DAGS
158.4TFA
0MWM
0MWL
267.7TFA
210.2TFA
118.9TFA

Properties (5)

additional_info
SC305318
custom_field_two
4
customer
LACSD
datetime
2016-03-17T02:10:33-07:00
sewer_category
GRAVITY