Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2016, 11:13 AM
  • 16 0505_16 0504 _20161118_031354.mp4

Date
11/18/2016
W/O
596918
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13556
Time
3:13 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3882
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
WO_596918_TV16026_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
16 0505
Downstream MH
16 0504
Dir. of Survey
Downstream
Length Surveyed
291.1 ft.
Total Length
291.1 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 16 0505 to 16 0504
MH: 16 0505MH: 16 0504downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05050 ft. MWM - Water Mark, 20 %of cross sectional area3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.2 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"7.2 ft. VC - Vermin Cockroach45.2 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"69.9 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"132.7 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 6", 1"184.4 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"225.1 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"276.3 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES287.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish291 ft. MGO - General Observation - LATERAL AT MH 3 O CLOCK ACTIVE291.1 ft. AMH - Downstream Manhole, Survey Ends - 16 0504

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    7.2 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    45.2 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    69.9 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

    132.7 ft. - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    184.4 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    225.1 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    276.3 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
3.1DAGS
7.2TBA
291MGOLATERAL AT MH 3 O CLOCK ACTIVE
225.1TBA
0MWL
45.2TBA
132.7TBI
184.4TBA
0AMH16 0505
0MWM
276.3CL
7.2VC
287.9DAGS
291.1AMH16 0504
69.9TBA

Properties (5)

additional_info
SC305215
custom_field_two
4
customer
LACSD
datetime
2016-11-18T03:13:35-08:00
sewer_category
Gravity