Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2016, 11:07 AM
  • 21 0996_21 0995_20160427_052448.mp4

Date
04/27/2016
W/O
557418
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00784
PipeID
P16096
Time
4:07 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3192
Sewer Name
21 SAN ANTONIO TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
09
Purpose
Routine Assessment
Project
WO_557418_TV21023_APRIL2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
21 0996
Downstream MH
21 0995
Dir. of Survey
Downstream
Length Surveyed
360.8 ft.
Total Length
360.8 ft.
Structural Index
4
Structural Quick
4300
Structural Rating
12
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 21 0996 to 21 0995
MH: 21 0996MH: 21 0995downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 09969.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"12.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES31.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES34.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"55.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"58.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start130.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"134.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"183.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"190.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"256.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"311.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"358.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish360.8 ft. AMH - Downstream Manhole, Survey Ends - 21 0995

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    12.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    31.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    58.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
9.3TFC
0MWL
55.7TFC
190.4TF
183.8TFC
130.7TFC
360.8AMH21 0995
0VC
311.9TF
34.5TF
256.8TF
134.1TF
31.6FM
12.9FM
358.3FM
0MWM
0AMH21 0996
58.9FM

Properties (5)

additional_info
SC226240
custom_field_two
2
customer
LACSD
datetime
2016-04-27T04:07:38-07:00
sewer_category
FACILITY TO FACILITY