Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2017, 06:29 AM
  • 32 0132_32 0131A_14092017_233902.mp4

Date
09/14/2017
W/O
658035
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00887
PipeID
P19879
Time
11:29 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4875
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_658035_TV32048_SEP2017
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0132
Downstream MH
32 0131A
Dir. of Survey
Downstream
Length Surveyed
279.5 ft.
Total Length
279.5 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
280
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole 32 0132 to 32 0131A
MH: 32 0132MH: 32 0131Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 01322 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK279.5 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish279.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279.5 ft. AMH - Downstream Manhole, Survey Ends - 32 0131A

Observation photos (2)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
279.5MGOCONNECTION AT MH 3 O'CLOCK
279.5SAP
0MWM
279.5SSS
2SAP
279.5AMH32 0131A
2SSS
0AMH32 0132

Properties (5)

additional_info
SC345934
custom_field_two
2
customer
LACSD
datetime
2017-09-14T23:29:29-07:00
sewer_category
Gravity