- Date
- 09/20/2017
- W/O
- 658035
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00887
- PipeID
- P23687
- Time
- 1:52 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4882
- Sewer Name
- 32 DISTRICT #32 MAIN TRUNK
- City
- SANTA CLARITA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 32
- Page No.
- 08
- Purpose
- Routine Assessment
- Project
- WO_658035_TV32048_SEP2017
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Width
- 30 in.
- Upstream MH
- 32 0109
- Downstream MH
- 32 0261
- Dir. of Survey
- Downstream
- Length Surveyed
- 162.6 ft.
- Total Length
- 162.7 ft.
- Structural Index
- 3
- Structural Quick
- 513E
- Structural Rating
- 159
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 159
Pipe schematic from manhole 32 0109 to 32 0261 Observation photos (3)

2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

17 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

146 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES