Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2015, 05:33 AM
  • 22 1362_22 1361_20150420_223903.mp4

Date
04/20/2015
W/O
496785
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00795
PipeID
P16643
Time
10:33 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2359
Sewer Name
22 CAMERON RELIEF TRUNK
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
WO_496785_TV22009_2015MARCH
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
22 1362
Downstream MH
22 1361
Dir. of Survey
Downstream
Length Surveyed
138.3 ft.
Total Length
138.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 22 1362 to 22 1361
MH: 22 1362MH: 22 1361downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 13620 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start122.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"137.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish138.3 ft. AMH - Downstream Manhole, Survey Ends - 22 1361

Observation photos (7)

  • Upstream Manhole, Survey Begins - 22 1362

    0 ft. - Upstream Manhole, Survey Begins - 22 1362

  • Water Level, 10 %of cross sectional area

    0 ft. - Water Level, 10 %of cross sectional area

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    122.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Finish

    137.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish

  • Downstream Manhole, Survey Ends - 22 1361

    138.3 ft. - Downstream Manhole, Survey Ends - 22 1361

Observations (7)

DistanceCodeObservation
137.7DAGS
122.5TB
0AMH22 1362
2.2DAGS
0MWL
0MWM
138.3AMH22 1361

Properties (6)

additional_info
SC200712
custom_field_two
4
customer
LACSD
datetime
2015-04-20T22:33:56-07:00
sewer_category
GRAVITY
year_laid
19890123