Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2014, 06:14 AM
  • 22 0272A_22 0272_20141222_222429.mp4

Date
12/22/2014
W/O
480783
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00793
PipeID
P16558
Time
10:14 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K1987-SC189552
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_480783_TV22015_2014DECEMBER
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
22 0272A
Downstream MH
22 0272
Dir. of Survey
Downstream
Length Surveyed
168.4 ft.
Total Length
168.4 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
96
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
96
Pipe schematic from manhole 22 0272A to 22 0272
MH: 22 0272AMH: 22 0272downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22150 ft. MWL - Water Level, 20 %of cross sectional area0 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 8"4.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"9.9 ft. MGO - General Observation - MAG COATING THROUGHOUT PIPE86.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"110.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"126.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"166.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish168.4 ft. AMH - Downstream Manhole, Survey Ends - 2224

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT PIPE

    9.9 ft. - General Observation - MAG COATING THROUGHOUT PIPE

Observations (12)

DistanceCodeObservation
0MWM
9.9MGOMAG COATING THROUGHOUT PIPE
168.4AMH2224
0AMH2215
126.9TF
86.7TFC
166.2SAP
110.8TFC
0MWL
6.1TFC
4.4SAP
0TFA

Properties (4)

custom_field_two
CR 3
customer
LACSD
datetime
2014-12-22T22:14:23-08:00
sewer_category
GRAVITY