Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2017, 07:34 AM
  • J 0396_J 0395_1122017_013847.mp4

Date
11/02/2017
W/O
0624519
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P21088
Time
12:34 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0667
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Routine Assessment
Project
20171102MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0396
Downstream MH
J 0395
Dir. of Survey
Downstream
Length Surveyed
360.4 ft.
Total Length
360.4 ft.
Structural Index
2
Structural Quick
372A
Structural Rating
46
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
46
Pipe schematic from manhole J 0396 to J 0395
MH: J 0396MH: J 0395downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:25AM0 ft. MWM - Water Mark, 30 %of cross sectional area25.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT33.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE47.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE61.8 ft. FS - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE61.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE63.3 ft. CC - Crack Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES85 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H110.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H110.4 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H110.4 ft. MGO - General Observation - 27" VCP124.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H146.1 ft. FS - Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT146.1 ft. FS - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE155.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H160 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL160 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL172.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H184.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H194.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL243.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL257.9 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE257.9 ft. FS - Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES, Finish - SLIGHT292.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL332.9 ft. FS - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE358 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H360.4 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (6)

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT

    25.9 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    47.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    61.8 ft. - Fracture Spiral, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • General Observation - 27" VCP

    110.4 ft. - General Observation - 27" VCP

  • Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    146.1 ft. - Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    257.9 ft. - Fracture Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

Observations (29)

DistanceCodeObservation
146.1FSSLIGHT
124.5FCH
110.4FCH
0MWL
85FCH
160FCSL
184.3FCH
63.3CC
292.1FCSL
243.3FCSL
0AMH1:25AM
160FCSL
33.8FLHAIRLINE
47.2FLHAIRLINE
332.9FSHAIRLINE
172.8FCH
257.9FSHAIRLINE
257.9FSSLIGHT
146.1FSHAIRLINE
61.8FSHAIRLINE
0MWM
25.9FLSLIGHT
110.4FCH
155.7FCH
110.4MGO27" VCP
358FCH
360.4AMH2:05AM
61.8FLHAIRLINE
194.1FLSL

Properties (5)

custom_field_three
SLIGHT SPRIAL FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-11-02T00:34:04-07:00
year_laid
19950221