Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 26, 2017, 07:26 AM
  • 02 0388_02 0387_10262017_011853.mp4

Date
10/26/2017
W/O
0640865
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00325
PipeID
P08298
Time
12:26 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H 0659
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
SAN GABRIEL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
10252017VMR_JOA-IA_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0388
Downstream MH
02 0387
Dir. of Survey
Downstream
Length Surveyed
405.1 ft.
Total Length
405.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 02 0388 to 02 0387
MH: 02 0388MH: 02 0387downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:21 AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SZC - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - Mag Coat 9:00 to 3:00133.1 ft. MGO - General Observation - Patch of missing mag coat403.5 ft. SZC - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - Mag coat 9:00 to 3:00405.1 ft. AMH - Downstream Manhole, Survey Ends - 01:16 AM

Observation photos (1)

  • General Observation - Patch of missing mag coat

    133.1 ft. - General Observation - Patch of missing mag coat

Observations (7)

DistanceCodeObservation
0AMH12:21 AM
2SZCMag Coat 9:00 to 3:00
0MWM
403.5SZCMag coat 9:00 to 3:00
0MWL
405.1AMH01:16 AM
133.1MGOPatch of missing mag coat