Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2017, 07:54 AM
  • 04 0005_04 0004_10212017_013426.mp4

Date
10/21/2017
W/O
0630073
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00408
PipeID
P11735
Time
12:54 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0655
Sewer Name
04 DISTRICT #4 OUTFALL TRUNK
City
Beverly Hills
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
10202017VMR_DISTRICT_4_OUTFALL_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
04 0005
Downstream MH
04 0004
Dir. of Survey
Downstream
Length Surveyed
540 ft.
Total Length
540 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 04 0005 to 04 0004
MH: 04 0005MH: 04 0004downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:38 AM0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - Slight2 ft. SZC - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - Mag Coat 60-80%537.7 ft. SZC - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - Mag Coat 60-80%537.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish540 ft. AMH - Downstream Manhole, Survey Ends - 01:40 AM

Observations (8)

DistanceCodeObservation
537.7SZCMag Coat 60-80%
540AMH01:40 AM
0AMH12:38 AM
537.7SAV
0MWM
2SAVSlight
2SZCMag Coat 60-80%
0MWL

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-10-21T00:54:58-07:00