Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2017, 09:34 AM
  • C 0687_C 0114 _09082017_023625.mp4

Date
09/08/2017
W/O
651655
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00126
PipeID
P24970
Time
2:34 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4963
Sewer Name
C JOINT OUTFALL C - UNIT 4A
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Routine Assessment
Project
WO_651655_TV03069_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
C 0687
Downstream MH
C 0114
Dir. of Survey
Downstream
Length Surveyed
89.4 ft.
Total Length
89.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4132
O&M Rating
48
Overall Index
2
Overall Quick
Overall Rating
48
Pipe schematic from manhole C 0687 to C 0114
MH: C 0687MH: C 0114downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 06872 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start19.2 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start88 ft. MGO - General Observation - SPALLING FROM 08 TO 04 O'CLOCK THROUGHOUT THE REACH89.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish89.4 ft. AMH - Downstream Manhole, Survey Ends - C 011489.4 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish89.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
89.4DAGS
2DAGS
88MGOSPALLING FROM 08 TO 04 O'CLOCK THROUGHOUT THE REACH
89.4AMHC 0114
0MWM
2.9DAE
89.4DSC
0MWL
89.4DAE
0AMHC 0687
19.2DSC

Properties (5)

additional_info
SC345954
custom_field_two
3
customer
LACSD
datetime
2017-09-08T02:34:48-07:00
sewer_category