- Date
- 09/11/2017
- W/O
- 651628
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00473
- PipeID
- P07009
- Time
- 11:35 PM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4870
- Sewer Name
- 05 LOMITA TRUNK EXTENSION
- City
- TORRANCE
- Loc. details
- Parking Lot
- Location Code
- G
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 32
- Purpose
- Routine Assessment
- Project
- WO_651628_TV05200_AUG2017
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 05 1778
- Downstream MH
- 05 1778A
- Dir. of Survey
- Upstream
- Length Surveyed
- 9.6 ft.
- Total Length
- 9.6 ft.
- Structural Index
- 3
- Structural Quick
- 4121
- Structural Rating
- 6
- O&M Index
- 1
- O&M Quick
- 1100
- O&M Rating
- 1
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 7
Pipe schematic from manhole 05 1778 to 05 1778A Observation photos (3)

4.3 ft. - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

4.3 ft. - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

7.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES