Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2017, 08:23 AM
  • 22 1388_22 0268_24012017_002408.mp4

Date
01/24/2017
W/O
613443
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16553
Time
12:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4132
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_613443_TV22016_JAN2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 1388
Downstream MH
22 0268
Dir. of Survey
Downstream
Length Surveyed
45.5 ft.
Total Length
45.5 ft.
Structural Index
3
Structural Quick
3900
Structural Rating
27
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole 22 1388 to 22 0268
MH: 22 1388MH: 22 0268downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 6 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 13880 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start11.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start45.5 ft. AMH - Downstream Manhole, Survey Ends - 22 026845.5 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish45.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish45.5 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO, Start

    11.8 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start

Observations (11)

DistanceCodeObservation
11.8DSZ
45.5AMH22 0268
0MWM
2SAP
45.5SAP
45.5DSZ
0MGOCONNECTION AT THE MH 3 O'CLOCK
0MGOCONNECTION AT THE MH 6 O'CLOCK
0AMH22 1388
45.5MGOCONNECTION AT THE MH 9 O'CLOCK
0MWL

Properties (5)

additional_info
SC306488
custom_field_two
3
customer
LACSD
datetime
2017-01-24T00:23:37-08:00
sewer_category
Gravity