- Date
- 01/25/2017
- W/O
- 613443
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00793
- PipeID
- P16535
- Time
- 12:21 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4133
- Sewer Name
- 22 CAMERON TRUNK, SECTS 1,2,&3
- City
- WEST COVINA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 36
- Purpose
- Routine Assessment
- Project
- WO_613443_TV22016_JAN2017
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 22 0253
- Downstream MH
- 22 0252
- Dir. of Survey
- Downstream
- Length Surveyed
- 359.2 ft.
- Total Length
- 359.2 ft.
- Structural Index
- 3
- Structural Quick
- 3M11
- Structural Rating
- 214
- O&M Index
- 1
- O&M Quick
- 2112
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 218
Pipe schematic from manhole 22 0253 to 22 0252 Observation photos (4)

3.1 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

7.3 ft. - Crack Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

64.3 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

268.4 ft. - Roots Fine Barrell, at 10 o'clock, within 8 inches of joint: NO