Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2017, 11:17 AM
  • 22 0262_22 0261 _24012017_031824.mp4

Date
01/24/2017
W/O
613443
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16544
Time
3:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4132
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_613443_TV22016_JAN2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0262
Downstream MH
22 0261
Dir. of Survey
Downstream
Length Surveyed
313.9 ft.
Total Length
313.9 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
186
Pipe schematic from manhole 22 0262 to 22 0261
MH: 22 0262MH: 22 0261downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02622.1 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start11.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"108.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"313.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK313.9 ft. AMH - Downstream Manhole, Survey Ends - 22 0261313.9 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
108.3TFC
228.5TFC
11.5TF
105.1TFC
313.9MGOCONNECTION AT THE MH 9 O'CLOCK
2.1SAP
0MGOCONNECTION AT THE MH 9 O'CLOCK
0MWL
313.9AMH22 0261
0MWM
59.7TFC
313.9SAP
210.5TFC
258.9TFC
159.4TFC
0AMH22 0262

Properties (5)

additional_info
SC306488
custom_field_two
3
customer
LACSD
datetime
2017-01-24T03:17:49-08:00
sewer_category
Gravity