Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2017, 10:47 AM
  • 22 0249_22 0248 _25012017_024759.mp4

Date
01/25/2017
W/O
613443
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16531
Time
2:47 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4133
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_613443_TV22016_JAN2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0249
Downstream MH
22 0248
Dir. of Survey
Downstream
Length Surveyed
290.1 ft.
Total Length
290.1 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
3
O&M Quick
4111
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
179
Pipe schematic from manhole 22 0249 to 22 0248
MH: 22 0249MH: 22 0248downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 02490 ft. MWL - Water Level, 15 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start14.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"24.8 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YESR68.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"80.4 ft. RBL - Roots Ball Lateral, at 02 o'clock, 65 %, within 8 inches of joint: NO80.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"212 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"257.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"290.1 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish290.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0248

Observation photos (2)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YESR

    24.8 ft. - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YESR

Observations (19)

DistanceCodeObservation
257.6TF
14.5TFC
212TFC
158.3TF
161.2TFC
265.9TFC
0MWM
0MGOCONNECTION AT THE MH 3 O'CLOCK
290.1SAP
0AMH22 0249
0MWL
113.2TFC
2.2SAP
24.8RFJ
68.5TFC
23.5TFC
80.4RBL
290.1AMH22 0248
80.4TF

Properties (5)

additional_info
SC306489
custom_field_two
3
customer
LACSD
datetime
2017-01-25T02:47:28-08:00
sewer_category
Gravity