Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2017, 09:43 AM
  • 22 0266_22 0265_24012017_014359.mp4

Date
01/24/2017
W/O
613443
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00793
PipeID
P16549
Time
1:43 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4132
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_613443_TV22016_JAN2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0266
Downstream MH
22 0265
Dir. of Survey
Downstream
Length Surveyed
430.3 ft.
Total Length
430.3 ft.
Structural Index
3
Structural Quick
3a00
Structural Rating
510
O&M Index
1
O&M Quick
2113
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
515
Pipe schematic from manhole 22 0266 to 22 0265
MH: 22 0266MH: 22 0265downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02662 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"131.2 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR140.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.6 ft. RFL - Roots Fine Lateral, at 10 o'clock156.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"241 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"313.3 ft. RFB - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: NO341.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"385.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"390.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"408.7 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR422.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"430.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish430.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0265430.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

    131.2 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR

  • Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: NO

    313.3 ft. - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: NO

  • Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR

    408.7 ft. - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR

Observations (24)

DistanceCodeObservation
156.6RFL
156.6TF
341.4TFC
430.3SAP
309.4TF
2SAP
430.3AMH22 0265
0MWM
148.8TF
430.3CM
313.3RFB
131.2RFJ
10CM
0MWL
39.9TFC
192.6TFC
0AMH22 0266
241TFC
140.9TFC
92.3TFC
385.9TFC
390.1TFC
422.2TFA
408.7RFJ

Properties (5)

additional_info
SC306488
custom_field_two
3
customer
LACSD
datetime
2017-01-24T01:43:24-08:00
sewer_category
Gravity