Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2017, 09:28 AM
  • B 0411_B 0410_1202017_024601.mp4

Date
01/20/2017
W/O
0607729
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00092
PipeID
P08923
Time
1:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO405
Sewer Name
B JOINT OUTFALL B - UNIT 5B
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
03
Purpose
Routine Assessment
Project
20170120MDM_JOINT_OUTFALL_B_UNIT_5B
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 0411
Downstream MH
B 0410
Dir. of Survey
Downstream
Length Surveyed
397.9 ft.
Total Length
397.9 ft.
Structural Index
2
Structural Quick
3A2D
Structural Rating
79
O&M Index
2
O&M Quick
3112
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole B 0411 to B 0410
MH: B 0411MH: B 0410downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 4 O' Clock. Capped0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active4 ft. RMJ - Roots Medium Joint, from 10 to 02 o'clock, 10 %, within 8 inches of joint: YESR12.4 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT16.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE24.4 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H24.4 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL28.5 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - H32.5 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR - 1%36.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL36.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H44.8 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 2%52.7 ft. FC - Fracture Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES - H56.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H57 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H64.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H80.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H84.6 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H93.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped100.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H103.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H107.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H131.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H134.9 ft. MGO - General Observation - 18" VCP163.7 ft. FC - Fracture Circumferential, from 09 to 01 o'clock, within 8 inches of joint: YES - SL163.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL168.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H173 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped174.5 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL182.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H186.8 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H190.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H202.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H203 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active217.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H245.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H255.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped280.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H285.1 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H285.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H309.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H309.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H310.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped317.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped348.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H367.3 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL397.6 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped397.6 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN397.9 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (1)

  • General Observation - 18" VCP

    134.9 ft. - General Observation - 18" VCP

Observations (52)

DistanceCodeObservation
0AMH2:45AM
24.4FCH
52.7FCH
173TFCCapped
186.8FCH
163.7FCSL
182.7FLH
56.1FLH
134.9MGO18" VCP
174.5FCSL
397.6MGOConn. @ Mh, 3 O' Clock. Capped
348.3FCH
285.1FCH
84.6FCH
0MWL
255.3TFCCapped
4RMJ
310.5TFCCapped
285.1FLH
32.5RFJ1%
202.9FLH
203TFActive
217.6FCH
64.7FCH
16.4FCHAIRLINE
309.6FLH
57FLH
190.6FLH
367.3FCSL
163.7FCSL
0MWM
24.4FCSL
280.9FCH
44.8RFJ2%
28.5FCH
131.7FLH
80.9FCH
12.4FCSLIGHT
168.1FCH
100.2FLH
245.9FCH
93.9TFCCapped
36.5FCSL
36.5FCH
309.6FLH
0MGOConn. @ Mh, 4 O' Clock. Capped
397.9AMH3:30AM
0MGOConn. @ Mh, 3 O' Clock. Active
103.2FCH
107.6FLH
317.2TFCCapped
397.6MGOConn. @ Mh, 9 O' Clock. OPEN

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime