Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2017, 09:13 AM
  • B 0424_B 0423_1132017_030625.mp4

Date
01/13/2017
W/O
0607729
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00092
PipeID
P08936
Time
1:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0394
Sewer Name
B JOINT OUTFALL B - UNIT 5B
City
SIERRA MADRE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
03
Purpose
Routine Assessment
Project
20170113MDM_JOINT_OUTFALL_B_UNIT_5B
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 0424
Downstream MH
B 0423
Dir. of Survey
Downstream
Length Surveyed
170.9 ft.
Total Length
170.9 ft.
Structural Index
2
Structural Quick
352A
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
37
Pipe schematic from manhole B 0424 to B 0423
MH: B 0424MH: B 0423downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:00AM10 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE17.9 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT17.9 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE26.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H30.8 ft. MGO - General Observation - 18" VCP43.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H46.4 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H67.3 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - H80.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped97.8 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL106.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL110.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H131.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL135.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H142.8 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H156 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open158 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL158 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H167.7 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H170.9 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observation photos (1)

  • General Observation - 18" VCP

    30.8 ft. - General Observation - 18" VCP

Observations (23)

DistanceCodeObservation
110.2FCH
156TFOpen
30.8MGO18" VCP
167.7FCH
17.9FCSLIGHT
80.6TFCCapped
10FCHAIRLINE
0MWL
0MWM
142.8FCH
158FCSL
170.9AMH3:20AM
46.4FCH
97.8FCSL
17.9FCHAIRLINE
158FLH
135.2FCH
106.4FCSL
0AMH3:00AM
67.3FLH
26.7FLH
43.1FLH
131.6FLSL

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2017-01-13T01:13:14-08:00