Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2017, 09:50 AM
  • Section#1_05 1849_05 1848__10102017__G6846.mp4

Date
10/10/2017
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00494
PipeID
P07074
Time
2:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6846
Sewer Name
05 NORTH SLOPE CONNECTION TRUNK
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
20171010MDM_NORTH_SLOPE_CONNECTION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
05 1849
Downstream MH
05 1848
Dir. of Survey
Downstream
Length Surveyed
401.2 ft.
Total Length
401.2 ft.
Structural Index
2
Structural Quick
3224
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole 05 1849 to 05 1848
MH: 05 1849MH: 05 1848downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. AMH - Upstream Manhole, Survey Begins - 3:05AM16.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT16.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL16.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES84.6 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL110.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN162.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN172 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE172.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN212 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN247.2 ft. MGO - General Observation - 18" VCP262.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN267 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H299.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN359 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN401.2 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM

Observation photos (1)

  • General Observation - 18" VCP

    247.2 ft. - General Observation - 18" VCP

Observations (19)

DistanceCodeObservation
0MWL
16.5FCSLIGHT
172FLHAIRLINE
359TFOPEN
0MWM
212TFOPEN
162.4TFOPEN
0MGOMH CONN ACTIVE 9:00
84.6FCSL
0AMH3:05AM
110.5TFOPEN
267FLH
299.5TFOPEN
16.5FCSL
262.7TFOPEN
16.5FC
172.5TFOPEN
401.2AMH3:35AM
247.2MGO18" VCP

Properties (4)

custom_field_three
FEW SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2017-10-10T02:50:39-07:00