Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2017, 05:04 AM
  • 05 1387_05 1386 _30082017_220509.mp4

Date
08/30/2017
W/O
652020
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06607
Time
10:04 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4804
Sewer Name
05 MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
WO_652020_TV05074_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1387
Downstream MH
05 1386
Dir. of Survey
Downstream
Length Surveyed
293.1 ft.
Total Length
293.1 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
171
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
171
Pipe schematic from manhole 05 1387 to 05 1386
MH: 05 1387MH: 05 1386downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13870 ft. MWL - Water Level, 10 %of cross sectional area3.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"58.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"109 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"290.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK293.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK293.1 ft. AMH - Downstream Manhole, Survey Ends - 05 1386

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
208.2TFC
4.8TF
109TF
0MWM
224.3TF
0AMH05 1387
290.7CM
293.1MGOCONNECTION AT MH 3 O'CLOCK
58.3TF
160.4TFC
293.1MGOCONNECTION AT MH 9 O'CLOCK
0MWL
3.2CM
293.1AMH05 1386

Properties (5)

additional_info
SC345913
custom_field_two
3
customer
LACSD
datetime
2017-08-30T22:04:32-07:00
sewer_category
Gravity