Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2017, 09:04 AM
  • 05 1375_05 1374 _31082017_020502.mp4

Date
08/31/2017
W/O
652020
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06594
Time
2:04 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4804
Sewer Name
05 MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
WO_652020_TV05074_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1375
Downstream MH
05 1374
Dir. of Survey
Downstream
Length Surveyed
338.4 ft.
Total Length
338.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1375 to 05 1374
MH: 05 1375MH: 05 1374downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13750 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area2.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"122 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"178 ft. MGO - General Observation - PIPE CHIPPING AWAY 12 TO 01 O'CLOCK235.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"338.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1374338.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED338.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish338.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    302.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
338.4AMH05 1374
0MWL
173.4TF
0AMH05 1375
75.9TFC
178MGOPIPE CHIPPING AWAY 12 TO 01 O'CLOCK
302.2TB
284.1TFC
122TFC
330.4TFC
338.4MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM
37.4TFC
235.3TFC
338.4CM
2.7CM
338.4MGOCONNECTION AT MH 9 O'CLOCK CAPPED

Properties (5)

additional_info
SC345913
custom_field_two
3
customer
LACSD
datetime
2017-08-31T02:04:28-07:00
sewer_category
Gravity