Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2017, 07:42 AM
  • 05 1397_05 1396 _30082017_004405.mp4

Date
08/30/2017
W/O
652020
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06618
Time
12:42 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4803
Sewer Name
05 MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_652020_TV05074_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1397
Downstream MH
05 1396
Dir. of Survey
Downstream
Length Surveyed
318.5 ft.
Total Length
318.5 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
191
Pipe schematic from manhole 05 1397 to 05 1396
MH: 05 1397MH: 05 1396downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 13970 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK3.6 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES6.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start69.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"245 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"291.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES293.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED318.5 ft. AMH - Downstream Manhole, Survey Ends - 05 1396

Observation photos (3)

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    3.6 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES

    291.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
0AMH05 1397
116.3TF
6.6CM
245TF
3.6CM
0MWM
69.9TFC
318.5MGOCONNECTION AT MH 9 O'CLOCK CAPPED
293.8TF
316.1CM
291.9DAGS
0MGOCONNECTION AT MH 3 O'CLOCK
154.7TF
0MWL
318.5AMH05 1396
0MGOCONNECTION AT MH 9 O'CLOCK
201.3TF

Properties (5)

additional_info
SC345912
custom_field_two
3
customer
LACSD
datetime
2017-08-30T00:42:53-07:00
sewer_category
Gravity