Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2017, 08:12 AM
  • 05 1377_05 1376 _31082017_011243.mp4

Date
08/31/2017
W/O
652020
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06596
Time
1:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4804
Sewer Name
05 MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
WO_652020_TV05074_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1376
Downstream MH
05 1377
Dir. of Survey
Upstream
Length Surveyed
292.5 ft.
Total Length
292.5 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
174
Pipe schematic from manhole 05 1376 to 05 1377
MH: 05 1376MH: 05 1377upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 05 13770 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish76.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"178.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"263.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"287.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start292.5 ft. AMH - Downstream Manhole, Survey Begins - 05 0176292.5 ft. MWM - Water Mark, 20 %of cross sectional area292.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK292.5 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH05 0176
0MWM
29.1TF
95.8TF
0MGOCONNECTION AT MH 9 O'CLOCK
4.6CM
292.5MGOCONNECTION AT MH 3 O'CLOCK
292.5AMH05 1377
0MWL
292.5CM
167.9TFA
216.2TF
114.2TF

Properties (5)

additional_info
SC345913
custom_field_two
3
customer
LACSD
datetime
2017-08-31T01:12:02-07:00
sewer_category