Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 09:44 AM
  • 05 0964_05 0963 _06072017_034444.mpg

Date
07/06/2017
W/O
630086
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00481
PipeID
P06196
Time
2:44 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4552
Sewer Name
05 MANCHESTER AVENUE PUMP TRUNK
City
HAWTHORNE
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
WO_630086_TV05069_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0963
Downstream MH
05 0964
Dir. of Survey
Upstream
Length Surveyed
297.7 ft.
Total Length
297.7 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 0963 to 05 0964
MH: 05 0963MH: 05 0964upstream0 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 09640 ft. MGO - General Observation - CONNECTION AT 3 OC0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish24.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"76.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"113 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 4"118.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"124.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"176.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"226.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start230.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"238.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES279.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"287.5 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES295.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start297.7 ft. AMH - Downstream Manhole, Survey Begins - 05 0963297.7 ft. MWM - Water Mark, 25 %of cross sectional area297.7 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    10.2 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    59.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    71.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
297.7CL
59.6CL
173TFC
297.7AMH05 0964
221.5TFC
0AMH05 0963
2.3DAGS
17.9TFC
0MWM
184.7TB
297.7MGOCONNECTION AT 3 OC
273TFC
121.5TFC
297.7DAGS
178.9TBA
0MWL
66.8TFC
10.2CM
71.4CL

Properties (5)

additional_info
SC345383
custom_field_two
3
customer
LACSD
datetime
2017-07-06T02:44:16-07:00
sewer_category