Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2017, 11:15 AM
  • 05 0948_05 0947 _17072017_043334.mp4

Date
07/17/2017
W/O
630086
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00481
PipeID
P06180
Time
4:15 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4659
Sewer Name
05 MANCHESTER AVENUE PUMP TRUNK
City
HAWTHORNE
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_630086_TV05069_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0947
Downstream MH
05 0948
Dir. of Survey
Upstream
Length Surveyed
269 ft.
Total Length
269 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 0947 to 05 0948
MH: 05 0947MH: 05 0948upstream0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"51.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"102.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"111.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"149.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 1"201.6 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"224 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start253 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"259 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES267 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start269 ft. MSA - Survey Abandoned - REVERSAL COMPLETE269 ft. AMH - Downstream Manhole, Survey Begins - 05 0947269 ft. MWM - Water Mark, 45 %of cross sectional area269 ft. MWL - Water Level, 15 %of cross sectional area269 ft. MGO - Reversal Inspection

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    10 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    45 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
2DAGS
0MSAREVERSAL COMPLETE
217.7TFC
0AMH05 0947
67.4TFA
0MWM
10CL
0MWL
269CM
16TFC
269DAGS
166.1TFC
157.6TF
0MGO
45CM
119.1TFC
268TFC

Properties (5)

additional_info
SC345397
custom_field_two
3
customer
LACSD
datetime
2017-07-17T04:15:59-07:00
sewer_category
Gravity