Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 07:36 AM
  • 05 0948_05 0947 _06072017_005930.mpg

Date
07/06/2017
W/O
630086
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00481
PipeID
P06180
Time
12:36 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4552
Sewer Name
05 MANCHESTER AVENUE PUMP TRUNK
City
HAWTHORNE
Loc. details
Railway
Location Code
L
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_630086_TV05069_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 0948
Downstream MH
05 0947
Dir. of Survey
Downstream
Length Surveyed
194.4 ft.
Total Length
194.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 05 0948 to 05 0947
MH: 05 0948MH: 05 0947downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 09482.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start16.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"68 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"121.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"168.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"194.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish194.4 ft. MSA - Survey Abandoned - GREASE194.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
121.5TFC
194.4DAGS
194.4MSAGREASE
7.2CM
0MWM
194.4CM
0MWL
0AMH05 0948
2.5DAGS
16.4TFC
68TFC
168.6TFC

Properties (5)

additional_info
SC345383
custom_field_two
5
customer
LACSD
datetime
2017-07-06T00:36:49-07:00
sewer_category