- Date
- 07/27/2016
- W/O
- 568720
- Weather
- Dry
- Operator/Surveyor
- J. HARTOOG
- Sewer ID
- Z00349
- PipeID
- P02998
- Time
- 1:10 AM
- Certificate
- U-507-03-3386
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K3664
- Sewer Name
- 02 DISTRICT #2 INTERCEPTOR TRUNK
- City
- COMMERCE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 17
- Purpose
- Routine Assessment
- Project
- WO_568720_TV02317_JUNE2016
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 54 in.
- Width
- 54 in.
- Upstream MH
- 02 1426
- Downstream MH
- 02 1425
- Dir. of Survey
- Downstream
- Length Surveyed
- 843.4 ft.
- Total Length
- 843.4 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 3
- O&M Quick
- 4222
- O&M Rating
- 12
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole 02 1426 to 02 1425 Observation photos (3)

7.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

412.6 ft. - Deposits Attached Ragging, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES

499.2 ft. - General Photograph