Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2017, 10:31 AM
  • H 1371_H 1370 _061317_033253.mp4

Date
06/13/2017
W/O
641138
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z01187
PipeID
P26168
Time
3:31 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4549
Sewer Name
H JOINT OUTFALL H - UNIT 5D RELIEF
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_641138_TV15216_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 1370
Downstream MH
H 1371
Dir. of Survey
Upstream
Length Surveyed
343.3 ft.
Total Length
343.3 ft.
Structural Index
2
Structural Quick
2M00
Structural Rating
136
O&M Index
2
O&M Quick
2W00
O&M Rating
244
Overall Index
2
Overall Quick
Overall Rating
380
Pipe schematic from manhole H 1370 to H 1371
MH: H 1370MH: H 1371upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 13710 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish1.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish271.5 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start338.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start341.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start343.3 ft. MWM - Water Mark, 25 %of cross sectional area343.3 ft. AMH - Downstream Manhole, Survey Begins - H 1370343.3 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
4.4DAGS
0MWM
342SSS
0AMHH 1370
343.3AMHH 1371
0MWL
343.3DAGS
71.8DSC
343.3DSC
2SSS

Properties (6)

additional_info
SC345364
custom_field_two
3
customer
LACSD
datetime
2017-06-13T03:31:25-07:00
sewer_category
Gravity
year_laid
40073