Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2017, 08:29 AM
  • 08 0467_08 0466_912017_020522.mp4

Date
09/01/2017
W/O
0660368
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00523
Time
1:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H0633
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Maintenance Related
Project
20170901MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0467
Downstream MH
08 0466
Dir. of Survey
Downstream
Length Surveyed
157.8 ft.
Total Length
157.8 ft.
Structural Index
5
Structural Quick
5300
Structural Rating
15
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
19
Pipe schematic from manhole 08 0467 to 08 0466
MH: 08 0467MH: 08 0466downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM1 ft. MGO - General Observation - MH# 4672 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING,BROKEN LONG & CIRCUM REBAR8 ft. MGO - General Observation - 36" RCP CTL18.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR68.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - MIISING REBAR108.1 ft. MGP - General Photograph157.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN157.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - MISSING BROKEN LONG CIRCUM REBAR157.8 ft. AMH - Downstream Manhole, Survey Ends - 2:15AM

Observation photos (6)

  • General Observation - MH# 467

    1 ft. - General Observation - MH# 467

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING,BROKEN LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - MISSING,BROKEN LONG & CIRCUM REBAR

  • General Observation - 36" RCP CTL

    8 ft. - General Observation - 36" RCP CTL

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    18.7 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - MIISING REBAR

    68.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - MIISING REBAR

  • General Photograph

    108.1 ft. - General Photograph

Observations (12)

DistanceCodeObservation
68.1SRCMIISING REBAR
108.1MGP
157.2MGOConn. @ Mh, 3 O' Clock. OPEN
2SRCMISSING,BROKEN LONG & CIRCUM REBAR
1MGOMH# 467
0MWL
0MWM
8MGO36" RCP CTL
0AMH1:55AM
157.8AMH2:15AM
18.7SRCHANGING REBAR
157.2SRCMISSING BROKEN LONG CIRCUM REBAR

Properties (4)

custom_field_three
MISSING BROKEN REBAR
custom_field_two
1
customer
LACSD
datetime
2017-09-01T01:29:24-07:00