Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 2, 2017, 08:54 AM
  • Section#4_G 0316_G 0315__1022017__G6834.mp4

Date
10/02/2017
W/O
0646225
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00228
PipeID
P01752
Time
1:54 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6835
Sewer Name
G JOIINT OUTFALL G- UNIT 9 TRUNK
City
SOUTH GATE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Capital Improvement Program Assesment
Project
20171002MDM_JOINT_OUTFALL_G_UNIT_9_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
G 0316
Downstream MH
G 0315
Dir. of Survey
Downstream
Length Surveyed
197.8 ft.
Total Length
197.8 ft.
Structural Index
4
Structural Quick
544G
Structural Rating
176
O&M Index
3
O&M Quick
3G00
O&M Rating
117
Overall Index
4
Overall Quick
Overall Rating
293
Pipe schematic from manhole G 0316 to G 0315
MH: G 0316MH: G 0315downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES5.8 ft. MGO - General Observation - 90% MISSING TILES7.6 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR8.8 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - FALLEN TILES & DEBRIE10.6 ft. MGO - General Observation - MISSING TILES 30% START21.9 ft. MGO - General Observation - MISSING TILES 90%24.5 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR34.1 ft. MGO - General Observation - 90% MISSING TILES49.6 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - FALLEN TILES DEBRIE49.6 ft. MGO - General Observation - MISSING TILES 90%78.2 ft. MGO - General Observation - 90% MISSING TILES84.9 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR94.3 ft. MGO - General Observation - 90% MISSING TILES97.3 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR105.9 ft. MGO - General Observation - 90% MISSING TILES127.2 ft. MGO - General Observation - 90% MISSWING TILES138.5 ft. MGO - General Observation - 80% MISSING TILES151.5 ft. MGO - General Observation - 60% MISSING TILES162.8 ft. MGO - General Observation - 50% MISSING TILES192.5 ft. MGO - General Observation - DEBRI ON CABLE197.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES197.4 ft. MGO - General Observation - MISSING TILES 30% FINISH197.4 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - TILES & DEBRIE197.8 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (19)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES

  • General Observation - 90% MISSING TILES

    5.8 ft. - General Observation - 90% MISSING TILES

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

    7.6 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

  • General Observation - MISSING TILES 30% START

    10.6 ft. - General Observation - MISSING TILES 30% START

  • General Observation - MISSING TILES 90%

    21.9 ft. - General Observation - MISSING TILES 90%

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    24.5 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 90% MISSING TILES

    34.1 ft. - General Observation - 90% MISSING TILES

  • Deposits Settled Other,  20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO - FALLEN TILES DEBRIE

    49.6 ft. - Deposits Settled Other, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - FALLEN TILES DEBRIE

  • General Observation - MISSING TILES 90%

    49.6 ft. - General Observation - MISSING TILES 90%

  • General Observation - 90% MISSING TILES

    78.2 ft. - General Observation - 90% MISSING TILES

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    84.9 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • General Observation - 90% MISSING TILES

    94.3 ft. - General Observation - 90% MISSING TILES

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    97.3 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 90% MISSING TILES

    105.9 ft. - General Observation - 90% MISSING TILES

  • General Observation - 90% MISSWING TILES

    127.2 ft. - General Observation - 90% MISSWING TILES

  • General Observation - 80% MISSING TILES

    138.5 ft. - General Observation - 80% MISSING TILES

  • General Observation - 60% MISSING TILES

    151.5 ft. - General Observation - 60% MISSING TILES

  • General Observation - 50% MISSING TILES

    162.8 ft. - General Observation - 50% MISSING TILES

  • General Observation - DEBRI ON CABLE

    192.5 ft. - General Observation - DEBRI ON CABLE

Observations (27)

DistanceCodeObservation
197.4SAMSEVERE AGG AREAS OF MISSING TILES
192.5MGODEBRI ON CABLE
21.9MGOMISSING TILES 90%
5.8MGO90% MISSING TILES
197.8AMH5:10AM
78.2MGO90% MISSING TILES
97.3SRVCIRCUM REBAR
94.3MGO90% MISSING TILES
197.4MGOMISSING TILES 30% FINISH
49.6DSZFALLEN TILES DEBRIE
0MWM
138.5MGO80% MISSING TILES
0MWL
49.6MGOMISSING TILES 90%
24.5SRVCIRCUM REBAR
84.9SRVCIRCUM REBAR
127.2MGO90% MISSWING TILES
151.5MGO60% MISSING TILES
162.8MGO50% MISSING TILES
10.6MGOMISSING TILES 30% START
0AMH4:35AM
7.6SRCLONG REBAR
8.8DSZFALLEN TILES & DEBRIE
2SAMAREAS OF MISSING TILES
34.1MGO90% MISSING TILES
197.4DSZTILES & DEBRIE
105.9MGO90% MISSING TILES

Properties (4)

custom_field_three
LONG & CIRCUM REBAR
custom_field_two
1
customer
LACSD
datetime
2017-10-02T01:54:16-07:00