Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2017, 06:19 AM
  • 02 2176_02 2175 _23082017_232023.mp4

Date
08/23/2017
W/O
652201
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00261
PipeID
P04450
Time
11:19 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4792
Sewer Name
02 FOSTER ROAD TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
WO_652201_TV02290_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 2176
Downstream MH
02 2175
Dir. of Survey
Downstream
Length Surveyed
178.4 ft.
Total Length
178.4 ft.
Structural Index
2
Structural Quick
2F00
Structural Rating
70
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole 02 2176 to 02 2175
MH: 02 2176MH: 02 2175downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 21760 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0.1 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start175 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish178.4 ft. AMH - Downstream Manhole, Survey Ends - 02 2175178.4 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observations (8)

DistanceCodeObservation
0MWL
178.4AMH02 2175
178.4MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0AMH02 2176
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
0.1MWM
175SSS
2SSS

Properties (6)

additional_info
SC345901
custom_field_two
3
customer
LACSD
datetime
2017-08-23T23:19:51-07:00
sewer_category
Gravity
year_laid
31114