Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 24, 2017, 06:50 AM
  • 02 2174_02 2173 _23082017_235022.mp4

Date
08/23/2017
W/O
652201
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00261
PipeID
P04448
Time
11:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4792
Sewer Name
02 FOSTER ROAD TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
WO_652201_TV02290_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 2174
Downstream MH
02 2173
Dir. of Survey
Downstream
Length Surveyed
261.5 ft.
Total Length
261.5 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
104
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
104
Pipe schematic from manhole 02 2174 to 02 2173
MH: 02 2174MH: 02 2173downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 21742 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start260 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish261.4 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH261.5 ft. AMH - Downstream Manhole, Survey Ends - 02 2173

Observations (8)

DistanceCodeObservation
0MWM
2SSS
0MWL
261.4MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
260SSS
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
261.5AMH02 2173
0AMH02 2174

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2017-08-23T23:50:16-07:00
sewer_category
Gravity
year_laid