Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2017, 07:15 AM
  • 22 0967_22 0966_22082017_003305.mp4

Date
08/22/2017
W/O
651622
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00790
PipeID
P17337
Time
12:15 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4694
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
WO_651622_TV22002_AUG2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0967
Downstream MH
22 0966
Dir. of Survey
Downstream
Length Surveyed
375.1 ft.
Total Length
375.1 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 22 0967 to 22 0966
MH: 22 0967MH: 22 0966downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 09673.1 ft. MGO - General Observation - MAG COATING3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.1 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MAG COATING151.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"212.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"316.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"375.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0966, MAG COAT THROUGHOUT THE REACH375.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish375.1 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MAG COATING

    3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MAG COATING

Observations (14)

DistanceCodeObservation
0MWL
3.1MGOMAG COATING
375.1AMH22 0966, MAG COAT THROUGHOUT THE REACH
0MWM
3.1DAGS
3.1SRI
375.1DAGS
375.1SRI
212.1TF
3.1SSSMAG COATING
0AMH22 0967
316.6TFC
375.1SSS
151.3TFC

Properties (5)

additional_info
SC345633
custom_field_two
3
customer
LACSD
datetime
2017-08-22T00:15:56-07:00
sewer_category