Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 22, 2017, 10:30 AM
  • 22 0962_22 0961_22082017_034904.mp4

Date
08/22/2017
W/O
651622
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00790
PipeID
P17332
Time
3:30 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4694
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
WO_651622_TV22002_AUG2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0962
Downstream MH
22 0961
Dir. of Survey
Downstream
Length Surveyed
288.2 ft.
Total Length
288.2 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 22 0962 to 22 0961
MH: 22 0962MH: 22 0961downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 09620 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MAG COATING3.7 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.7 ft. MGO - General Observation - MAG COATING14.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"54.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"78.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"106.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"136.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4", 4"157.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"205.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"212.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"255.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"255.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"288.2 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish288.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0961, MAG COAT THROUGHOUT THE REACH288.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MAG COATING

    3.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MAG COATING

  • Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
205.5TFC
255.7TF
288.2SRI
0AMH22 0962
0MWL
0MWM
78.4TFC
2.5DAGS
3.7SSSMAG COATING
157.6TFC
14.4TFC
255.8TF
136.8TF
106.1TF
3.7SRI
288.2DAGS
288.2AMH22 0961, MAG COAT THROUGHOUT THE REACH
288.2SSS
212.9TFC
54.5TFC
3.7MGOMAG COATING

Properties (5)

additional_info
SC345633
custom_field_two
3
customer
LACSD
datetime
2017-08-22T03:30:28-07:00
sewer_category