Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 23, 2017, 09:47 AM
  • 22 0982_22 0981_23082017_025655.mp4

Date
08/23/2017
W/O
651862
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00790
PipeID
P17352
Time
2:47 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4696
Sewer Name
22 BASE LINE TRUNK
City
GLENDORA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
05
Purpose
Routine Assessment
Project
WO_651862_TV22001_AUG2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0982
Downstream MH
22 0981
Dir. of Survey
Downstream
Length Surveyed
222.8 ft.
Total Length
222.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 22 0982 to 22 0981
MH: 22 0982MH: 22 0981downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 09823.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"16.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"28.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"69.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"80.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"139.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"151 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"204.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"222.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish222.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0981222.8 ft. MGO - General Observation - CONNECTION AT 9 OC

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
80.6TFC
222.8DAGS
0MWM
151TF
69.4TF
3.1DAGS
0MWL
16.8TFC
204.6TFC
11.9TF
0AMH22 0982
222.8AMH22 0981
222.8MGOCONNECTION AT 9 OC
28.2TF
139.8TFC

Properties (4)

additional_info
SC345635
custom_field_two
4
customer
LACSD
datetime
2017-08-23T02:47:03-07:00