Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2017, 12:10 PM
  • 05 2602_05 2601 _30052017_051607.mp4

Date
05/30/2017
W/O
641198
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z01131
PipeID
P25307
Time
5:10 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4272
Sewer Name
05 COLDEN AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
08
Purpose
Routine Assessment
Project
WO_641198_TV05127_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2602
Downstream MH
05 2601
Dir. of Survey
Downstream
Length Surveyed
124.1 ft.
Total Length
124.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 05 2602 to 05 2601
MH: 05 2602MH: 05 2601downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 26020 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start120.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish124.1 ft. AMH - Downstream Manhole, Survey Ends - 05 2601

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0MWL
124.1AMH05 2601
0AMH05 2602
0MWM
120.4DAGS
2.1DAGS

Properties (5)

additional_info
SC345272
custom_field_two
5
customer
LACSD
datetime
2017-05-30T05:10:32-07:00
year_laid
38590