Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 06:23 AM
  • B 1138_B 1137_05072017_233357.mp4

Date
07/05/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13178
Time
11:23 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1138
Downstream MH
B 1137
Dir. of Survey
Downstream
Length Surveyed
284.2 ft.
Total Length
284.2 ft.
Structural Index
3
Structural Quick
3I23
Structural Rating
159
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
160
Pipe schematic from manhole B 1138 to B 1137
MH: B 1138MH: B 1137downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - B 11380 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area10.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES14.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES19.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES24.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"52.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"219.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"228 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"230.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"272.7 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES279.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"280.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish284.2 ft. AMH - Downstream Manhole, Survey Ends - B 1137

Observation photos (7)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    10.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    14.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    19.6 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    24.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    52.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    228 ft. - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    272.7 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
14.2CL
19.6CL
57.3TF
0MWM
24.1CM
133.4TFA
192.3TF
272.7RFJ
228TB
64.7TFC
279.3TF
148.6TF
152.1TF
0MGOCONNECTION AT MH 9 O'CLOCK
0AMHB 1138
33.5TF
219.3TF
52.9TB
0MGOCONNECTION AT MH 3 O'CLOCK
230.8TFC
284.2AMHB 1137
0MGOCONNECTION AT MH 6 O'CLOCK
280.7CM
0MWL
10.3CL
68.9TF

Properties (5)

additional_info
SC345428
custom_field_two
3
customer
LACSD
datetime
2017-07-05T23:23:32-07:00
sewer_category