Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 08:17 AM
  • B 1133_B 1132_06072017_011733.mp4

Date
07/06/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13173
Time
1:17 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1133
Downstream MH
B 1132
Dir. of Survey
Downstream
Length Surveyed
293.2 ft.
Total Length
293.2 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
146
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
146
Pipe schematic from manhole B 1133 to B 1132
MH: B 1133MH: B 1132downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11338.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES18.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"39.8 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES43.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"43.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.2 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES58.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start61.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"90.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"104.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"150 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"190.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"270.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"286.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish293.2 ft. AMH - Downstream Manhole, Survey Ends - B 1132

Observation photos (7)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    8.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    39.8 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    43.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    51.2 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    58.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    92.2 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    250.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (33)

DistanceCodeObservation
150TF
43.5TF
126.4TFC
51.2CM
250.7TF
46.6TF
8.8CL
104.1TF
58.9CM
61.6TFC
173.4TFC
43.7TB
0MGOCONNECTION AT MH 9 O'CLOCK
64.6TFC
0MWL
0MWM
203.2TFC
153.4TF
123.6TF
18.6TFC
183.3TFC
286.6CM
221.3TFC
293.2AMHB 1132
90.1TF
190.6TF
270.5TF
226.5TF
39.8CM
0AMHB 1133
250.5TB
92.2TB
239.9TFC

Properties (5)

additional_info
SC345428
custom_field_two
3
customer
LACSD
datetime
2017-07-06T01:17:18-07:00
sewer_category
Gravity