Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 30, 2017, 09:40 AM
Date
06/30/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13484
Time
2:40 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4634
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1163
Downstream MH
B 1164
Dir. of Survey
Upstream
Length Surveyed
603.5 ft.
Total Length
603.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1400
O&M Rating
4
Overall Index
1
Overall Quick
Overall Rating
7
Pipe schematic from manhole B 1163 to B 1164
MH: B 1163MH: B 1164upstream0 ft. MGO - General Observation - CONNECTION AT MH 12 ACTIVE0 ft. AMH - Upstream Manhole, Survey Ends - B 11640 ft. MGO - General Observation - CONNECTION AT MH 1 ACTIVE27.4 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES58.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"148.6 ft. RFL - Roots Fine Lateral, at 11 o'clock152.3 ft. CM - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES162.6 ft. RFL - Roots Fine Lateral, at 01 o'clock162.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"176.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"237.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"243.2 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"282.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"282.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"285.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"335.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"348.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"384.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"389.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"407.8 ft. RFJ - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES409.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"436.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"482.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"493.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"494.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"517.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"539.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"546.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"574.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"591.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"597.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"603.6 ft. AMH - Downstream Manhole, Survey Begins - B 1163603.6 ft. MWL - Water Level, 5 %of cross sectional area603.6 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (8)

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    29.4 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    110.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES

    195.8 ft. - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    320.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    360.4 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    441 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

    451.3 ft. - Crack Multiple, from 07 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES

    576.2 ft. - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES

Observations (36)

DistanceCodeObservation
64.4TFC
576.2RFJ
317.9TF
603.6MGOCONNECTION AT MH 12 ACTIVE
219.4TF
544.7TF
603.6AMHB 1164
427TF
0AMHB 1163
365.8TF
214.2TF
441RFL
455TF
120.9TF
29.4TB
57.4TF
451.3CM
167.3TF
360.4TBA
369.8TFC
194.5TF
195.8RFJ
455RFL
268.1TFC
320.8TBA
6.3TF
86.3TF
0MWL
12.3TFC
109.1TFC
441TB
110.5TB
0MWM
254.8TF
320.8TFC
603.6MGOCONNECTION AT MH 1 ACTIVE

Properties (5)

additional_info
SC345426
custom_field_two
4
customer
LACSD
datetime
2017-06-30T02:40:14-07:00
sewer_category
Gravity