Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 06:50 AM
  • B 1137_B 1136_05072017_235057.mp4

Date
07/05/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13177
Time
11:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
SOUTH PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1137
Downstream MH
B 1136
Dir. of Survey
Downstream
Length Surveyed
277.3 ft.
Total Length
277.3 ft.
Structural Index
3
Structural Quick
3G23
Structural Rating
132
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
135
Pipe schematic from manhole B 1137 to B 1136
MH: B 1137MH: B 1136downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11370 ft. MWL - Water Level, 5 %of cross sectional area22.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"26.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES32.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES38 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"42.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES47.4 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES57.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.5 ft. RML - Roots Medium Lateral, at 02 o'clock, 15 %, within 8 inches of joint: NO60.1 ft. MGO - General Observation - PIPE MISSING70.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start86.1 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"89.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"238.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"270.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish277.3 ft. AMH - Downstream Manhole, Survey Ends - B 1136

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    26.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    32.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    42.8 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    47.4 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • General Observation - PIPE MISSING

    60.1 ft. - General Observation - PIPE MISSING

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    70.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

    86.1 ft. - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    238.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (26)

DistanceCodeObservation
70.3CM
42.8CL
86.1TB
155.9TF
57.5TF
199.3TF
26.7CM
0MWM
277.3CM
47.4CL
239.2TF
238.3TB
277.3AMHB 1136
250.4TFC
148.5TF
89.6TFC
270.4TF
60.1MGOPIPE MISSING
57.5RML
104.4TF
0AMHB 1137
22.3TF
32.2CL
38TF
171.2TF
0MWL

Properties (5)

additional_info
SC345428
custom_field_two
3
customer
LACSD
datetime
2017-07-05T23:50:50-07:00
sewer_category