Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2017, 08:33 AM
  • B 1132_B 1131_06072017_013412.mp4

Date
07/06/2017
W/O
640678
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01125
PipeID
P13172
Time
1:33 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4635
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
ALHAMBRA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
WO_640678_TV16072_JUN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
B 1132
Downstream MH
B 1131
Dir. of Survey
Downstream
Length Surveyed
244.4 ft.
Total Length
244.4 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
141
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
141
Pipe schematic from manhole B 1132 to B 1131
MH: B 1132MH: B 1131downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11324.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start170.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"208.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish244.4 ft. AMH - Downstream Manhole, Survey Ends - B 1131244.4 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    189.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
241.1CM
0MWL
244.4AMHB 1131
196.1TFC
4.5CM
231.3TFC
208.9TFC
170.3TFC
0MWM
206.8TF
220.3TFC
244.4MGOCAPPED LATERAL 9 O'CLOCK @ MH
189.7TB
0AMHB 1132

Properties (5)

additional_info
SC345428
custom_field_two
3
customer
LACSD
datetime
2017-07-06T01:33:39-07:00
sewer_category
Gravity