Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 7, 2017, 10:35 AM
  • 03 0026_03 0025_07082017_041003.mp4

Date
08/07/2017
W/O
646534
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00366
PipeID
P05045
Time
3:35 AM
Certificate
U-7-715-070007-
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4677
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_646534_TV03011_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
03 0026
Downstream MH
03 0025
Dir. of Survey
Downstream
Length Surveyed
344.3 ft.
Total Length
344.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 03 0026 to 03 0025
MH: 03 0026MH: 03 0025downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 00262 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start43 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"92.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"142.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"191.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"241 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"290.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"340.1 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"344.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish344.3 ft. AMH - Downstream Manhole, Survey Ends - 03 0025

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0MWL
340.1TB
142.9TB
241TB
290.8TB
344.3DAGS
191.7TB
0MWM
92.5TB
0AMH03 0026
2DAGS
344.3AMH03 0025
43TB

Properties (5)

additional_info
SC345615
custom_field_two
4
customer
LACSD
datetime
2017-08-07T03:35:41-07:00
sewer_category