Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2017, 07:12 PM
  • 03 0082_03 0081_15082017_150554.mp4

Date
07/26/2017
W/O
1590881
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00366
PipeID
P05104
Time
12:12 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3993
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
05
Purpose
Routine Assessment
Project
WO_646534_TV03011_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
03 0082
Downstream MH
03 0081
Dir. of Survey
Downstream
Length Surveyed
138.7 ft.
Total Length
138.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2D00
O&M Rating
52
Overall Index
2
Overall Quick
Overall Rating
52
Pipe schematic from manhole 03 0082 to 03 0081
MH: 03 0082MH: 03 0081downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 00826 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"45.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"71 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"112 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"116.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"135.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish138.7 ft. AMH - Downstream Manhole, Survey Ends - 03 0081

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
7.1TF
0MWM
112TFC
0MWL
138.7AMH03 0081
45.1TFC
6DAGS
116.1TFC
0AMH03 0082
71TF
135.1DAGS

Properties (5)

additional_info
SC345560
custom_field_two
4
customer
LACSD
datetime
2017-07-26T12:12:30-07:00
sewer_category
Gravity