Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2017, 11:01 AM
  • 18 0927_18 0926 __081117_042813.mp4

Date
08/11/2017
W/O
646328
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00700
PipeID
P14775
Time
4:01 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4684
Sewer Name
18 SCOTT AVENUE TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_646328_TV18118_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0927
Downstream MH
18 0926
Dir. of Survey
Downstream
Length Surveyed
250.6 ft.
Total Length
250.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 18 0927 to 18 0926
MH: 18 0927MH: 18 0926downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 09270 ft. MWL - Water Level, 15 %of cross sectional area1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start25.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"29 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"61.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start78.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"81.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"131.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"142.2 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start177.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"177.8 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish181 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"227.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"230.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 4"250.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish250.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0926250.6 ft. MGO - General Observation - CONNECTION AT 9 OC250.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    1.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    61.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    142.2 ft. - Deposits Settled Fine, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
250.6DAGS
0MWM
25.6TF
0AMH18 0927
181TF
131.1TF
230.7TFC
250.6AMH18 0926
78.7TF
61.8CM
0MWL
177.8TFC
177.8DSF
250.6MGOCONNECTION AT 9 OC
1.8DAGS
81.6TF
142.2DSF
227.6TFC
250.6CM
29TF

Properties (5)

additional_info
SC345623
custom_field_two
3
customer
LACSD
datetime
2017-08-11T04:01:09-07:00
sewer_category
Gravity